By Ahmed El-Rasheed
For more information, please visit our website.
Introduction
Though often seen as minor components in electrical power systems, surge and lightning arresters perform the vital function of protecting assets against overvoltage transients in the supply system. These transients are produced by a wide range of issues including system faults, disconnections, reconnections, resonance, ferroresonance and lightning strikes. In this article, we will take a brief look at the functions and types of arrester, and also at recommended methods for testing them.
What do arresters do?
This article focuses on the use of arresters in power transmission and distribution systems, but similar devices are used in almost every area of electrical engineering. Whatever the application, the key function of an arrester is to prevent damage caused by voltage surges and lightning strikes. Arresters for use in power systems are available from a variety of manufacturers including ABB, Honeywell, Toshiba, Eaton, and Siemens. The characteristics and performance of arresters are covered by many national and international standards, but two of the most frequently referenced are IEEE C62.11 and IEC 60099-4. Many different types of surge and lightning arresters are available as can be seen in Figure 1. Arresters are usually categorised by voltage rating, and the most frequently encountered are:
Figure 1: Typical surge arresters
Whatever their application, surge arresters must be able to withstand the large amount of energy released by the current that flows in them when they are subjected to a surge voltage. Lightning strikes in particular can generate very high levels of energy in an arrester, and devices that are designed and rated to provide protection in such cases are usually referred to as lightning arresters. The need for lightning protection is graphically illustrated in Figure 2 which shows a voltage transformer before and after a lightning strike. Lightning arresters, provided that they had been properly selected and installed, would have diverted the energy from the lightning strike safely to earth, but in this case, the poorly protected transformer was destroyed.
Figure 2: Voltage transformer before and after a lightning strike
Arresters are installed in parallel with the equipment they are protecting. At normal operating voltages, the arresters have high resistance and little to no current flows through them. When they are subjected to a surge at a higher than normal voltage, the arresters change to a low resistance state and conduct heavily. As a result, the energy in the surge is diverted away from the equipment under protection and is channelled safely to earth. When the voltage across the arrester returns to normal, it reverts to its high resistance state.
To ensure that they provide the best possible protection and to guard against damage to adjacent equipment during a surge event, arresters must be carefully installed and solidly bonded to ground. Figure 3 shows examples of lightning arresters installed on transformer bushings.
Figure 3: Arresters on transformer bushings
What are arresters made of?
Most modern arresters are made of metal-oxide varistors (MOVs), which are semiconductor devices that are sensitive to voltage. At its rated operating voltage, an MOV behaves as an insulator, but at higher voltages it behaves as a conductor. Figure 4 shows the voltage/ current curve for a typical MOV at constant temperature. Note that the current scale is logarithmic so when the voltage across the MOV reaches the point at which it starts to conduct, the current increases very rapidly for only a small change in voltage.
Figure 4: V-1 curve for a typical metal-oxide varistor (From ABB Application Guideline - Overvoltage Protection in Medium Voltage Systems)
Referring to this curve, voltage Uc is the continuous operating voltage at which there is very little current flow in the arrester. Uref is the knee point voltage where the MOV starts to change to the low resistance state. Beyond this point, in Zone B, the resistance of the MOV falls rapidly. Upl is the peak permissible voltage, and the MOV may be damaged if it is subjected to higher voltages.
In practical devices, multiple MOVs are contained in a rigid insulating housing that is provided with heat dissipation vents or fins, as shown in Figure 5.
Testing and verifying arresters
Since a defective arrester will, in many cases, produce no warning symptoms under normal service conditions, regular checking is necessary to ensure that installed devices are still capable of providing the required protection against damage and potentially catastrophic failures. There are three main methods of carrying out these checks: visual inspection, passive infrared inspection and electrical testing.
Visual inspection
Visual inspection is the first and simplest step, but it must be carried out by trained engineers and technicians who carefully examine each arrester looking for cracks which might lead to malfunctioning under surge conditions. The inspectors also look for corrosion, frayed wiring connections, and signs of water intrusion. High-voltage arresters are sometimes fitted with surge counters and, if these are present, the count should be checked. Some manufacturers recommend a maximum number of surges that their product can withstand and, if this number has been reached, replacement should be scheduled.
The final part of the visual inspection is to compare the records of current coming into the facility and the amount of power being used. A trend of increased power consumption in a transmission or distribution facility is often an indication of developing faults and should be investigated further, bearing in mind that an efficiency drop is not always caused by a faulty arrester, but a faulty arrester can cause efficiency drops.
Thermal inspection
Thermal inspection of arresters is carried out using either permanently installed sensors or a thermal camera to detect hot spots resulting from power loss in the arrester. Ideally, the thermal sensors should be installed near power lines, transformers and similar locations where the arresters are used. With a thermal camera, inspectors can detect specific problems such as breakdowns in the wiring or cracks in the cooling vents, as shown in Figure 6. It is important to use the camera to view the arrester from all sides, as some faults affect only one side. It is also useful to look at thermal trends over long periods as these can reveal developing problems before they lead to outages or major faults.
Electrical tests
Electrical tests are carried out by certified inspector whose first task is to identify the main function of the device. The recommended procedure is for the inspector to record this along with the operating voltage, the range of voltage, power factor, frequency, range of frequency, power supply type, load limits, and more. The inspection report should also include details of the equipment maintenance record and the number of times the main circuit breaker has tripped. The tripping data is useful because if a surge arrester is not operating correctly, a common consequence is frequent operation of circuit breakers as overvoltages are not clamped effectively. After this background information is gathered, there are three main types of electrical test that can be carried out:
Electrical tests compared
In the field, a third harmonic analysis test can quantify the condition of the arrester in terms of the number of MOV elements that are still functioning, but it takes somewhat longer to complete than a watts loss test. The V-1 response test is an excellent way to verify the V-1 characteristics and show that the arrester is still functioning, but it can require very high test voltages (440 kV for a 220 kV rated arrester, for example). This might not be practical and there are important safety implications. The DC insulation test is a simple pass/fail test that produces results in just 60 seconds, but it is only suitable for low and medium voltage arresters.
Nevertheless, in applications where there is a large volume of arresters to examine, the DC insulation test saves time and delivers reliable results.
In summary, the simple DC insulation test is usually best for low and medium voltage arresters, while the watts loss test is often the most suitable option for high voltage and station-class arresters.
Use of the guard terminal
To obtain reliable results from DC insulation and watts (loss) tests, it is essential to take into account surface leakage. This is the current that flows through the resistance path provided by contamination (dirt and moisture) on the outer surface of the arrester, which, during testing, will be in a high resistance state – unless it is defective – and will therefore effectively behave as an insulator. Surface leakage is often neglected, but it is very much part of the measurement and it can dramatically affect the results. With a dirty arrester, the surface leakage current during a test can easily be greater than the current flowing through the arrester itself.
By using the guard terminal, the surface leakage current can be automatically measured and removed from the final result. This is important when high values of resistance are expected as they are when testing high voltage components like arresters. Arresters tend to have large surface areas that get exposed to contamination, resulting in high surface leakage.
Figure 7 shows how the parallel current path that flows through the outside surface of an arrester can give a false low resistance reading. In this example, the arrester has an internal resistance of 800 MΩ but there is an external leakage path with a resistance of just 4 MΩ in parallel with this. The measured value is, therefore, 3.98 MΩ, which gives a completely erroneous impression of the condition of the arrester.
Figure 8: Current flow when guard terminal is not used
Figure 9: Current flow when the guard terminal is used
Figures 8 and 9 compare the current flow during testing when the guard terminal is not used against when it is used. It can be seen that the guard terminal effectively diverts the surface leakage current away from the test circuit, thereby ensuring that it does not influence the test result.
Conclusions and recommendations
Surge and lightning arresters play an essential role in electrical power systems. Their inspection and testing are sometimes overlooked in favour of testing more costly assets, but their correct operation is necessary to ensure reliability of supply. Several North American electrical utilities have successfully implemented DC insulation resistance testing programs for arresters. All arresters are tested on delivery from manufacturers, then annually, and additionally after the occurrence of faults. The utilities that have implemented this program are benefitting from improved downtime and power quality metrics – not to mention additional cost savings because arresters that are still fully functional are no longer being condemned. The moral is simple: to save money and enhance reliability of service – inspect and test your arresters regularly!
ABB. (2018). Application Guideline Overvoltage Protection in Medium Voltage Systems
D. Hogue, 2013, Electrical Explosion Donnells Power House Strawberry, CA [Video] https://youtu.be/HICmYZY3prE, Northern California Power Agency (NCPA)
IEEE Standard for Metal-oxide Surge Arresters for AC Power Circuits (>1 kV), IEEE C62.11, 2012
J. Lundquist, L. Stenström, A. Schei, B. Hansen, “New Method for Measurement of the Resistive Leakage Currents of Metal-Oxide Surge Arresters in Service,” IEEE, 1989
J. Woodworth (2011), Arrester Reference Voltage. ArresterWorks. http://www.arresterworks.com/arresterfacts/pdf_files/ArresterFacts_027_ Arrester_Reference_Voltage.pdf
Megger (2006). A Stitch in Time: The complete guide to electrical insulation testing
Megger. (2005). Application guide for power factor testing of surge (lightning) arresters
Megger. (2018). 5 kV, 10 kV and 15 kV Insulation Testing – Use of Guard Terminal
Metal-oxide surge arresters without gaps for AC systems, IEC, 60099-4, 2014
INTELLIGENT WORK FORUMS
FOR ENGINEERING PROFESSIONALS
FIRST NAME
*
With competitive price and timely delivery, Hengfeng sincerely hope to be your supplier and partner.
LAST NAME
*
*
MESSAGE
*
ADDITIONAL DETAILS
Thanks. We have received your request and will respond promptly.
Log In
Are you an
Engineering professional?
Join Eng-Tips Forums!
*Eng-Tips's functionality depends on members receiving e-mail. By joining you are opting in to receive e-mail.
Promoting, selling, recruiting, coursework and thesis posting is forbidden.
Eng-Tips Posting Policies
Surge Arrestor Test
thread238-258351 Forum Search FAQs Links MVPsForum
Search
FAQs
Links
MVPs
(Electrical)
(OP)
5 Nov 09 20:34Any body is aware of Surge capacitor test standards?
(Electrical)
5 Nov 09 21:41The IEEE C62 series covers surge arresters. Was your question about surge arrester or surge capacitor test standards? Your title says one thing, your post another.
(Electrical)
(OP)
6 Nov 09 15:55The field technician did a Hi-Po testing for insulation on a 5KV surge capacitor. It turned out to be below NETA standard. I am looking for the test standard for the surge arrestor.
(Electrical)
8 Nov 09 10:30Two comments on dc testing of capacitors:1 - it may take a long time to reach steady state since you have to charge the capacitor. The one minute time listed in NETA probably applies to capacitors where both terminals can be isolated from case/ground (two bushings). I think one minute reading is meaningless.2 - steady state leakage current can be affected by porcelain coniditon.Other possibly useful tests:1 - visual inspection of oil filled capacitors looking for leaks.2 - power factor test of oil-filled capacitors.3 - capacitance test of caps which have multiple internal series elements. Shorted cap will be evident.Westinghouse has published some guidelines for hi-pot testing of dry surge capacitors in one applicaiton I am familiar with. I will take a look at that on Monday if I remember.I'll be interested to hear if you come accross any standards for surge capacitors.
=====================================
Eng-tips forums: The best place on the web for engineering discussions.
(Electrical)
8 Nov 09 10:31By the way I assume we're talking about dc hi-pot testing (that's what NETA MTS1 mentions). If ac, never mind.
=====================================
Eng-tips forums: The best place on the web for engineering discussions.
(Electrical)
9 Nov 09 02:06I would megger to determine it's not shorted at 5kV or less depending on rating and AC test using (120vac) line voltage and a multimeter to determine the actual capacitance and compare it to the nameplate (or a PF test set if handy to supply ac). But I am less concerned about standards and really want to know if it will work correctly.
(Electrical)
(OP)
9 Nov 09 15:34It is DC hi-pot test.
Please let us know here why this post is inappropriate. Reasons such as off-topic, duplicates, flames, illegal, vulgar, or students posting their homework.
Thank you for helping keep Eng-Tips Forums free from inappropriate posts.
The Eng-Tips staff will check this out and take appropriate action.
Click Here to join Eng-Tips and talk with other members! Already a Member? Login
For more information, please visit Arrester Leakage Current Test Kit.