How Does A Fuse Cutout Work

20 May.,2024

 

How Does A Fuse Cutout Work

Used on overhead transmission lines and taps to protect distribution transformers from current surges and overloads,An overcurrent caused by a fault in the transformer or user circuit can cause the fuse to melt and the switch mechanism to visibly open,Disconnect the transformer from the line. The device can also be opened manually by a utility line worker standing on the ground and using a long insulating rod called a "ground rod.",

Want more information on Outdoor Fused Cutouts? Feel free to contact us.

Fuse cutout

Combination of a fuse and a switch

Cutout (left) attached to a feeder line (connection at the right not shown). The lower wire goes to the transformer A set of pole top cutouts (with C-shaped bodies) protecting a transformer on a 12.47 kV distribution line. One fuse is blown and the tube is hanging down. Lightning arresters are mounted on the crossarm opposite the fuse cutouts. Fuse cutouts with V-shaped bodies.

In electrical distribution, a fuse cutout or cut-out fuse (often referred to as a cutout) is a combination of a fuse and a switch, used in primary overhead feeder lines and taps to protect distribution transformers from current surges and overloads. An overcurrent caused by a fault in the transformer or customer circuit will cause the fuse to melt and the switch mechanism to visibly open, disconnecting the transformer from the line. The device can also be opened manually by utility linemen standing on the ground and using a long insulating stick called a "hot stick".

Components

[

edit

]

A cutout and fuse assembly consist of three major components:

  • The cutout body, an open frame that supports the fuse holder and a ribbed porcelain or polymer insulator that electrically isolates the conductive portions of the assembly from the support to which the insulator is fastened.
  • The fuse holder, also called the "fuse tube" or "door", an insulating tube which contains the replaceable fuse element. When the contained fuse melts ("blows"), it opens the circuit, and the fuse holder drops out of the upper contact and hangs from a hinge on its lower end. This hanging fuse holder provides a visible indication that the fuse has operated and assurance that the circuit is open. The circuit can also be opened manually by pulling out the fuse holder using a hot stick. The fuse holder is typically made out of a fiberglass tube with a covering and metal contact points. As a fuse holder ages, the coating on the fiberglass will degrade and the fiberglass tube will start "shedding". The tube starts out with a pinkish hue then becomes white and then starts to "shed" fiberglass.
  • The fuse element, or "fuse link", is the replaceable portion of the assembly that melts and breaks the circuit when the electric current through it exceeds its rated current value. There are many types of fuse elements for many different uses such as a type T fuse also known as a "slow-blow fuse" being used for sidelines.

The fuse holder may be replaced by a solid blade, which would allow the fuse holder assembly to be used as a switch only.

Construction

For more information, please visit Overhead Power Line Accessories D Bracket.

[

edit

]

The fuse elements used in most distribution cutouts are tin or silver alloy wires that melt when subjected to high enough current. Ampere ratings of fuse elements vary from 1 ampere to 200 amperes but a solid door will allow the full 300 ampere capacity of the cutout to be utilized.

Cutouts are typically mounted about 20 degrees off vertical so that the center of gravity of the fuse holder is displaced and the fuse holder will rotate and fall open under its own weight when the fuse blows. Mechanical tension on the fuse link normally holds an ejector spring in a stable position. When the fuse blows, the released spring pulls the stub of the fuse link out of the fuse holder tube to reduce surge duration and damage to the transformer and fuse holder. This quenches any arc in the fuse holder.

Linemen from Huntsville Utilities replace a blown cutout fuse with a non-conductive extending pole tool on July 10th, 2022 in Huntsville, Alabama.

Each fuse holder typically has an attached pull ring that can be engaged by a hook at the end of a fiberglass hot stick operated by a lineworker standing on the ground or from a bucket truck, to manually open the switch. While often used for switching, the standard cutout shown is not designed to be manually opened under load. For applications where the switch is likely to be used to interrupt power manually, a "load break" version is available that has an attachment to quench the arc.

Standards

[

edit

]

Up until the mid-1990s each manufacturer used their own dimensional standards for cutout design; by the late 1990s most cutouts were of an "interchangeable design". This design allows for the interchangeable use of cutout bodies and fuse holders manufactured by different vendors.

Are you interested in learning more about is rubber an electrical insulator? Contact us today to secure an expert consultation!

  • Patent 1,939,371 — 1930 cutout with single hinge
  • Patent 2,176,227 — 1932 cutout with double hinge
  • Patent 2,519,289 — 1944 cutout with lightning arrestor inside the insulator
  • Patent 6,583,708B1 — recent cutout design